What form is a powerpact 4 panel board?
Form Type
Powerpact 4 panel boards are Form 3b type 2 as standard.
Form 4 type 2 & 6 can be achieved by use of individual disconnectable neutral links adjacent to breakers or by the use of 4 pole breakers. Outgoing terminals should be shrouded with long terminal shields. The main neutral bar either side of the incomer should be removed and discarded together with the connecting copper bar. The incoming breaker should be a 4 pole breaker
Powerpact 4 panel boards are Form 3b type 2 as standard.
Form 4 type 2 & 6 can be achieved by use of individual disconnectable neutral links adjacent to breakers or by the use of 4 pole breakers. Outgoing terminals should be shrouded with long terminal shields. The main neutral bar either side of the incomer should be removed and discarded together with the connecting copper bar. The incoming breaker should be a 4 pole breaker