How much space do I need around a GenieEvo switchgear?
GenieEvo should be installed in a clean, dry, well ventilated substation whose climatic conditions are controlled to stay within those specified in IEC 62271-200 clause 2.1.1. GenieEvo has been tested to IEC 62271-200 for internal arc classification AF and requires the following minimum dimensions:
  • From back of switchboard to rear wall - 800mm
  • From end of switchboard to side wall - 500mm
  • From floor to ceiling - 3000mm
A minimum operating space at front of switchboard - 1000mm

For more information please see Installation, operation and maintenance instructions .

Schneider Electric UK

How much space do I need around a GenieEvo switchgear?
GenieEvo should be installed in a clean, dry, well ventilated substation whose climatic conditions are controlled to stay within those specified in IEC 62271-200 clause 2.1.1. GenieEvo has been tested to IEC 62271-200 for internal arc classification AF and requires the following minimum dimensions:
  • From back of switchboard to rear wall - 800mm
  • From end of switchboard to side wall - 500mm
  • From floor to ceiling - 3000mm
A minimum operating space at front of switchboard - 1000mm

For more information please see Installation, operation and maintenance instructions .

Schneider Electric UK

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.