Search FAQs
What is the minimum distance between the Vigirex rectangular sensor and the following bending of the busbar?
Depending on the size of the sensor, the following minimum distances must be respected:
- 280 x 115 mm sensor -> the distance between the sensor and the busbar bending must be equal to, or higher than 25cm.
- 470 x 160 mm sensor -> the distance between the sensor and the busbar bending must be equal to, or higher than 30cm.
- 280 x 115 mm sensor -> the distance between the sensor and the busbar bending must be equal to, or higher than 25cm.
- 470 x 160 mm sensor -> the distance between the sensor and the busbar bending must be equal to, or higher than 30cm.
Released for:Schneider Electric UK
Explore more
Range:
Explore more
Range: