{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

Altivar drives, do I need a separate run command with preset speeds?

Issue:
Wondering If I need a separate run command with preset speeds, on Altivar drives

Product Line;
Altivar drives

Environment:
All

Cause:
N/A

Resolution:
Yes, a run command is needed and the preset speed is a separate logic input. Need both to be high, to run at the preset speed.

Schneider Electric UK

Explore more
Range:
Category:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:
Category: