Search FAQs
What is the minimum MCset switchgear substation ceiling height?
MCset requires a minimum of 4 meter ceiling height from floor to ceiling to allow the safe dissipation of hot arc gasses.
For all MCset switchgear configurations more than 25kA or ceiling height less than 4m anti-arcing tunnel is needed.
For more information please see MCset Civil engineering guide on Schneider web page.
For all MCset switchgear configurations more than 25kA or ceiling height less than 4m anti-arcing tunnel is needed.
For more information please see MCset Civil engineering guide on Schneider web page.
Released for:Schneider Electric UK
Explore more
Range:
Explore more
Range: