Search FAQs
What are the object supported for Get Attribute Single & Set Attribute Single services in DeviceNet protocol in VAMP relay
The list of object supported for Get Attribute Single & Set Attribute Single services in DeviceNet protocol in VAMP relay (Vamp 50,Vamp200, vamp300) are listed below.
Standard objects support the following services:
- Identity Object – Get Attribute Single (GAS)
- DeviceNet Object – Get Attribute Single (GAS) and Set Attribute Single (SAS)
- Assembly Object – Get Attribute Single (GAS) and Set Attribute Single (SAS)
- Connection Object – Get Attribute Single (GAS)
Standard objects support the following services:
- Identity Object – Get Attribute Single (GAS)
- DeviceNet Object – Get Attribute Single (GAS) and Set Attribute Single (SAS)
- Assembly Object – Get Attribute Single (GAS) and Set Attribute Single (SAS)
- Connection Object – Get Attribute Single (GAS)
Released for:Schneider Electric UK
Explore more
Range:
Explore more
Range: