Issue:
ATV212 stop button on the HMI disabling as an E-stop when in terminal control mode
Product Line:
ATV212, SFD212, SFD21
Environment:
All serial numbers
Cause:
Prevent "Flashing E" code. Prevent having to cycle power to clear the drive.
Resolution:
Stop/reset key.
The setting of parameter F734 determines whether it is possible to stop the drive by the Stop key which is located on the drive and graphic display option.
0 = [Enable] 1= [Disable]
Note:
LOSS OF CONTROL
You are going to disable the stop button located on the drive and graphic display option. Do not select 1 unless exterior stopping methods exist.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
ATV212 stop button on the HMI disabling as an E-stop when in terminal control mode
Product Line:
ATV212, SFD212, SFD21
Environment:
All serial numbers
Cause:
Prevent "Flashing E" code. Prevent having to cycle power to clear the drive.
Resolution:
Stop/reset key.
The setting of parameter F734 determines whether it is possible to stop the drive by the Stop key which is located on the drive and graphic display option.
0 = [Enable] 1= [Disable]
Note:
LOSS OF CONTROL
You are going to disable the stop button located on the drive and graphic display option. Do not select 1 unless exterior stopping methods exist.
Failure to follow these instructions can result in death, serious injury, or equipment damage.