{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
How can we help you today?
How to program an ATV32 to start stop from terminals and use dial for speed reference?

Issue:
Use Terminals for Start/Stop and Dial for Speed Ref on ATV32

Product Line:
Altivar 32

Environment:
All

Cause:
N/A

Resolution:
Go into CONF, FULL, CTL menu.
Set CHCF to SEP (hold 2 seconds)
FR1 to A1U1.
CD1 to TER.

Schneider Electric UK

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: