{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
How can we help you today?
Is it necessary to provide 230V voltage to CL1, CL2 terminals for the ATS01N209QN?
ATS01N209QN does not use external supply for control circuit.
External supply is needed only for:
ATS01N1..FT (CL1 - CL2 or 24V)
ATS01N2..LY (terminals 6-7)

Schneider Electric UK

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: