How do you attach a Tesys D Contactor with Everlink connections to the Thermal Overload LRD3**?
For the Tesys D with Everlink terminals the corresponding Thermal Overload LRD should also have Everlink Terminals

Below is a video showing how to make the connection:



The Contactors and Overloads that are compatible are shown in the table below:
Relay setting
range (A)
Contactor
Reference
Overload LRD
Reference
9…13D40A…D65ALRD313
12…18D40A…D65ALRD318
17…25D40A…D65ALRD325
23…32D40A…D65ALRD332
30…40D40A…D65ALRD340
37…50D40A…D65ALRD350
48…65D50A and D65ALRD365
62...80D80ALRD380

The coil voltage for the contactors is added to the end of the part number
e.g. for an 80a motor the contactor would be LC1D80A** where ** is the coil voltage

Common coil voltages are:
  • 110V AC - F7
  • 240V AC - U7
  • 415V AC - N7
  • 24V DC - BD
The Torque Setting are dependent on the cable size
  • 5 Nm: 25 mm2
  • 8 Nm: 35 mm2