{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
How can we help you today?
How to coordinate the start address of IOscanner at BMENOC0301 of M580 system to communicate with Quantum
Question:
How to coordinate the start address of IOscanner at BMENOC0301 of M580 system to communicate with Quantum?

Answer:
Inside IO scan configurator of M580 system, the RD Address/WR Address is referring to address of counterpart.
Since M580 starts from %MW0 while Quantum start from %MW1, you have to assign the address 99 at  M580 IOscan configurator to correspond to the address 100 at Quantum.

Schneider Electric UK

Attachment(s)
IOscan.png [331.49 KB]
Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: