NetBotz | How to update the Self-signed Certificate?
Issue:
How to update the Self-signed Certificate on NetBotz appliance?

Product Line:
NetBotz 355,450,455,570

Environment:
NetBotz (All Versions)

Cause:
The SSL Certificate needs to updated on the appliance

Resolution:

To update the SSL certificate follow the instructions below:

1. Be sure the appliance is registered with DNS and you can ping it by Fully Qualified Domain Name (FQDN). i.e. "ping netbotz.example.com"

2. Enable Telnet on the NetBotz appliance by using the following URL: http://botname/enabletelnet
Notes: a. Use HTTPS in the URL if HTTP is disabled. b. Replace 'botname' in the URL with the FQDN or IP address of your NetBotz Appliance.

3. Telnet to the NetBotz appliance using Windows Command Prompt, PuTTy, or any other Telnet client.
Username/password on v3.X.X or 4.X.X firmware is root/apc
Username/password on v2.X.X firmware is root/netbotz

4. Press Shift+X within 5 seconds after logging in to break to a command line interface where the next steps must be completed.

5. From the command line, run the following commands:
cd /opt/netbotz/bin
source ssl-cert-functions
update_nbSelfSignedCert

6. Reboot the appliance via Advanced View by going to Tools > Reboot Appliance.

Alternately, changing the hostname and rebooting the appliance will renew the self signed certificate. If desired it can be changed back and rebooted again.

Schneider Electric UK

NetBotz | How to update the Self-signed Certificate?
Issue:
How to update the Self-signed Certificate on NetBotz appliance?

Product Line:
NetBotz 355,450,455,570

Environment: 
NetBotz (All Versions)

Cause: 
The SSL Certificate needs to updated on the appliance

Resolution:

To update the SSL certificate follow the instructions below:

1. Be sure the appliance is registered with DNS and you can ping it by Fully Qualified Domain Name (FQDN). i.e. "ping netbotz.example.com" 

2. Enable Telnet on the NetBotz appliance by using the following URL: http://botname/enabletelnet 
Notes: a. Use HTTPS in the URL if HTTP is disabled. b. Replace 'botname' in the URL with the FQDN or IP address of your NetBotz Appliance. 

3. Telnet to the NetBotz appliance using Windows Command Prompt, PuTTy, or any other Telnet client. 
Username/password on v3.X.X or 4.X.X firmware is root/apc 
Username/password on v2.X.X firmware is root/netbotz 

4. Press Shift+X within 5 seconds after logging in to break to a command line interface where the next steps must be completed. 
 
5. From the command line, run the following commands: 
cd /opt/netbotz/bin 
source ssl-cert-functions 
update_nbSelfSignedCert 

6. Reboot the appliance via Advanced View by going to Tools > Reboot Appliance.

Alternately, changing the hostname and rebooting the appliance will renew the self signed certificate. If desired it can be changed back and rebooted again. 

Schneider Electric UK

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.