Why Don't My Relays and Analog Outputs Work Properly?

Article available in these languages: Spanish

Issue:
Relay and Analog Output not working on ATV630.

Product Line:
ATV630

Environment:
Output Phase Loss

Cause:
n/a

Resolution:
First check all the relay and analog output settings in menu 5.11.
Go to 5.12 ( Error/Warning handling) and scroll down to Output Phase loss- if you want to turn off the Output Phase Loss, set to Function Inactive ( DO NOT SET to No Error Triggered).