How do I enable / disable the Output Phase Loss function on the ATV31 / ATV312 series drives?
Issue:
Can I disable or enable output phase loss on ATV31 and ATV312? 

Product line:
ATV31 and ATV312

Environment:
All

Cause:
Clarification of product capabilities

Resolution.
Remove any run command present on the drive, this parameter can not be changed if a command to run is present.  Drive should show RDY on the screen.
Press the Enter button (large knob in the middle of the faceplate of the drive) and scroll to the FLt menu.  
Press Enter and scroll to OPL parameter.
Press Enter and choose between three settings:
     NO - Function inactive
     YES - Function activated, fault will be triggered by this function.
     OAC - Function activated, fault will NOT be triggered by this function but the output will be cut and no power will be applied to the motor.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.