{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

What is the recommended network configuration to upgrade Smartlink and PowerTag Link with EPC ?

Smartlink and PowerTag Link can only be upgraded with EcoStruxure Power Commission (EPC).

Avoid to upgrade Smartlink or PowerTag Link gateway through a network configuration using routers. The Firmware upgrade process may fail if you are using this configuration.

Best architecture to upgrade your Smartlink SI-D, SI-B or PowerTag Link is to be connected in Ethernet point to point.
If you cannot be connected in point to point, ensure you have only one Ethernet Switch between your Smartlink / PowerTag Link and EPC.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: