{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
How can we help you today?
How do I program the ATV320 for remote HMI control?
Issue:
Programming the ATV320 for remote HMI control.

Product line:
ATV320, ATV31 , ATV312

Environment:
All serial numbers

Cause:
Customer would like to control with VW3A1101

Resolution:
Set Ref 1B switching to Ref 1 ch
Set Ref 1 ch to HMI
Set Porfile (CHCF)  to SEP
Set Cmd switching (CCS) to Cd1
Set Cmd cd1 to HMI

Schneider Electric UK

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: