{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

Why I cannot discover my Smartlink or PowerTag Link connected to EcoStruxure Power Commission (EPC) ?

For Cybersecurity reasons the Modbus TCP setting might not be enabled by default when receiving the gateway. You need to activate the Modbus TCP feature in the embedded Web Pages of your gateway to make it discoverable by EPC.

Log in to your gateway and go to the SETTINGS meny -> COMMUNICATION -> IP NETWORK SERVICES -> and check that MODBUS TCP checkbox is enabled on port 502.

Try again to discover your Smartlink / PowerTag Link with EPC.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: