Why am I getting very frequent "a valid license not found" error in PME (Power Monitoring Expert).

Issue:
Very often PME machine encounters a licensing error. Once you restart Flexnet Licensing services then the issue resolves but again appears after a few days.

Product Line:
Power Monitoring Expert 8.x, Power Monitoring Expert 9, Power Monitoring Expert 2020

Environment:
Power Monitoring Expert licensing

Cause:
This issue is most likely to happen due to system date and time change. The licenses can become untrusted if there is a time change greater than about 5 minutes. It does not matter whether the time is changed manually or by auto-sync.

Resolution:
Investigate the auto time synchronization settings if the time is not changed manually. Check Windows System event log and there you are supposed to find entries like the one shown in the below screenshot.


Schneider Electric UK

Why am I getting very frequent "a valid license not found" error in PME (Power Monitoring Expert).

Issue:
Very often PME machine encounters a licensing error. Once you restart Flexnet Licensing services then the issue resolves but again appears after a few days.

Product Line:
Power Monitoring Expert 8.x, Power Monitoring Expert 9, Power Monitoring Expert 2020

Environment:
Power Monitoring Expert licensing
 
Cause:
This issue is most likely to happen due to system date and time change. The licenses can become untrusted if there is a time change greater than about 5 minutes. It does not matter whether the time is changed manually or by auto-sync.

Resolution:
Investigate the auto time synchronization settings if the time is not changed manually. Check Windows System event log and there you are supposed to find entries like the one shown in the below screenshot.


Schneider Electric UK

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.