{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

Can you provide the maximum Earth fault loop impedance (Zs) for circuit breakers fitted inside I Line Panel board?

Please find the attachment with the Earth fault loop impedance (Zs) for both the thermal magnetic devices and are electronic micrologic devices.
In order to comply with BS7671 Amendment 3: 2015, the figure in the attachment should be multiplied by Cmin .95
123

Schneider Electric UK

Attachment(s)

MCCB Trip Settings NSX (CDXAE, CHXAE & CNXAE) TMD Issue 1.pdfMCCB Trip Settings NSX (CDXAE, CHXAE & CNXAE) TMD Issue 1.pdf [217.13 KB]
MCCB Trip Settings NSX (CDXAE) Micrologic 2.2 Issue 1.pdfMCCB Trip Settings NSX (CDXAE) Micrologic 2.2 Issue 1.pdf [262.7 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: