Can you provide the Earth fault loop impedance (Zs) for the Domae MCBs?
Please find the list of Domae mcb's Earth fault loop impedance Zs values. In order to comply with BS7671 Amendment 3: 2015 the figure in attachment should be multiplied with C min .95

Schneider Electric UK

Attachment(s)
TRIP curve Zs DOM.pdf [11.12 KB]