{}

Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
How can we help you today?
Can the iC60H RCBO's be used on a 110V AC System?

A 110V version of the iC60H RCBO is available, which is suitable for use on a standard 0 - 110V AC TN-S earthing system

A suitable RCBO to use would be the A9D198** range - ** = Amperage of the RCBO

If the 110V AC supply is 55 -0- 55V AC, the iC60H2 RCBO must be used

A suitable RCBO to use would be the A9D192** range - ** = Amperage of the RCBO

For example, for 10A use A9D19210, this is a 2 pole RCBO that can be used on 55 - 0 - 55v AC networks

For more information on the above range,s please see pages 2/5 and 2/6 of the attachment

Schneider Electric UK

Attachment(s)
SE8863_ 2 Acti 9 MCBs RCCB.pdf [2.69 MB]
Can the iC60H RCBO's be used on a 110V AC System?

A 110V version of the iC60H RCBO is available, which is suitable for use on a standard 0 - 110V AC TN-S earthing system

A suitable RCBO to use would be the A9D198** range - ** = Amperage of the RCBO

If the 110V AC supply is 55 -0- 55V AC, the iC60H2 RCBO must be used

A suitable RCBO to use would be the A9D192** range - ** = Amperage of the RCBO

For example, for 10A use A9D19210, this is a 2 pole RCBO that can be used on 55 - 0 - 55v AC networks

For more information on the above range,s please see pages 2/5 and 2/6 of the attachment

Schneider Electric UK

Attachment(s)
SE8863_ 2 Acti 9 MCBs RCCB.pdf [2.69 MB]
Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.