The auxiliary power supply for the PM700 range of power meters has a voltage rating and consumption of :-
100 - 415V +/-10% AC, 5VA.
125 - 250 +/-20% DC, 3W.
E.g 5VA = 0.02A However we dont offer a device at this rating so we would advise using a 2A mcb.
The auxiliary power supply for the PM800 range of power meters has a voltage rating and consumption of :-
100 - 415V +/-10% AC, 15VA with options.
125 - 250 +/-20% DC, 10W with options.
E.g 15VA = 0.06A However we dont offer a device at this rating so we would advise using a 2A mcb.
Therefore, the fuse rating will depend on how many meters are supplied ,and the size of the cable used to feed them.
100 - 415V +/-10% AC, 5VA.
125 - 250 +/-20% DC, 3W.
E.g 5VA = 0.02A However we dont offer a device at this rating so we would advise using a 2A mcb.
The auxiliary power supply for the PM800 range of power meters has a voltage rating and consumption of :-
100 - 415V +/-10% AC, 15VA with options.
125 - 250 +/-20% DC, 10W with options.
E.g 15VA = 0.06A However we dont offer a device at this rating so we would advise using a 2A mcb.
Therefore, the fuse rating will depend on how many meters are supplied ,and the size of the cable used to feed them.
Released for:Schneider Electric UK
The auxiliary power supply for the PM700 range of power meters has a voltage rating and consumption of :-
100 - 415V +/-10% AC, 5VA.
125 - 250 +/-20% DC, 3W.
E.g 5VA = 0.02A However we dont offer a device at this rating so we would advise using a 2A mcb.
The auxiliary power supply for the PM800 range of power meters has a voltage rating and consumption of :-
100 - 415V +/-10% AC, 15VA with options.
125 - 250 +/-20% DC, 10W with options.
E.g 15VA = 0.06A However we dont offer a device at this rating so we would advise using a 2A mcb.
Therefore, the fuse rating will depend on how many meters are supplied ,and the size of the cable used to feed them.
100 - 415V +/-10% AC, 5VA.
125 - 250 +/-20% DC, 3W.
E.g 5VA = 0.02A However we dont offer a device at this rating so we would advise using a 2A mcb.
The auxiliary power supply for the PM800 range of power meters has a voltage rating and consumption of :-
100 - 415V +/-10% AC, 15VA with options.
125 - 250 +/-20% DC, 10W with options.
E.g 15VA = 0.06A However we dont offer a device at this rating so we would advise using a 2A mcb.
Therefore, the fuse rating will depend on how many meters are supplied ,and the size of the cable used to feed them.