What current rating of fuse is required to protect the power supply on the PM700 and PM800 range of panel meters?
The auxiliary power supply for the PM700 range of power meters has a voltage rating and consumption of :-
100 - 415V +/-10% AC, 5VA.
125 - 250 +/-20% DC, 3W.
E.g 5VA = 0.02A However we dont offer a device at this rating so we would advise using a 2A mcb.

The auxiliary power supply for the PM800 range of power meters has a voltage rating and consumption of :-
100 - 415V +/-10% AC, 15VA with options.
125 - 250 +/-20% DC, 10W with options.
E.g 15VA = 0.06A However we dont offer a device at this rating so we would advise using a 2A mcb.

Therefore, the fuse rating will depend on how many meters are supplied ,and the size of the cable used to feed them.

Schneider Electric UK

What current rating of fuse is required to protect the power supply on the PM700 and PM800 range of panel meters?
The auxiliary power supply for the PM700 range of power meters has a voltage rating and consumption of :-
100 - 415V +/-10% AC, 5VA.
125 - 250 +/-20% DC, 3W.
E.g 5VA = 0.02A However we dont offer a device at this rating so we would advise using a 2A mcb.

The auxiliary power supply for the PM800 range of power meters has a voltage rating and consumption of :-
100 - 415V +/-10% AC, 15VA with options.
125 - 250 +/-20% DC, 10W with options.
E.g 15VA = 0.06A However we dont offer a device at this rating so we would advise using a 2A mcb.

Therefore, the fuse rating will depend on how many meters are supplied ,and the size of the cable used to feed them.
 

Schneider Electric UK

Explore more
Product:
Explore more
Product:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
Explore more
Product:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.