Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Why is the kW (Active Power) showing a negative reading on the Powerlogic series of meter?

A negative kW reading is usually due to one of 2 things

The Current transformers (CT's) have been fitted onto the cable or busbar the wrong way round.
The P1 side of the CT should be towards the supply and the P2 side of the CT should be towards the load.

Alternatively, if the CT is fitted correctly, the problem could be due to the secondary wiring from the CT to the meter being incorrectly connected.
Please check the wiring diagram of your chosen model to confirm the current inputs are wired correctly.

If you followed the above steps and you still experience the same issue, please contact us or reach out to support team.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings