{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
How can we help you today?
What would cause the ATV320 series Drive to still trip on OBF if the DB resistor has been installed?

Issue:

ATV320 Drive is tripping on OBF after installing the DB resistor.

Product Line:

ATV320...... C version.

Environment:

All

Cause:

DC bus is still over charging on ramp down.

Resolution:

-Check to make sure the Jumper factory jumper is still installed between PO and PA+ ( C suffix version Drives only)

-Check to make sure the DB resistor is wired between PO and PB.

-Power down the drive, let the DC bus discharge then check the DB resistors value across PO and PB. (Drive needs to be powered OFF to do this test)

-Check the programming under FUN, rPt the bRA to make sure its set to NO.

-Verify the correct DB resistor size has been installed.

Schneider Electric UK

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: