Why my new STBNIP2xxx device does not communicate with my old BMXNOC0401

The ethernet hardware part of the BMXNOC0401 PV01 has compatibilities problem with ethernet hardware part of last STBNIP2xxxx modules.
The solution is use a BMXNOC0401 with a PV > 1 or use other communication module like BMXNOE01xx.