what is the recommended torque settings for a 13a socket Ultimate Screwless flat Plate

The torque values for terminal screws is information that historically has not been provided by accessory suppliers.

However, in this particular instance, the “Ultimate Screwless, 13A, 2 gang switch socket,  has been tested and certified to the BS 1363-2. For this particular product and terminal screw size, this standard specifies a tightening torque of 0.8Nm for the verification of the mechanical strength of the screw and terminal assembly.

Therefore, we believe that a tightening torque value of 0.6 to 0.8 Nm should be appropriate for this product. This is of course also dependant on the installation and the size and number of cables being connected. Judgment should therefore be used to ensure the terminal screws are sufficiently tight for any given application.

Schneider Electric UK

Explore more
Product:
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Product:
Range:
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.