{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
How can we help you today?
Why are the REAL data type variables data not showing correctly in Vijeo Designer when communicating to a Unity Quantum PLC?

Issue:
REAL data type variables data not showing correctly in Vijeo Designer when communicating to a Unity Quantum PLC


Product Line:
Vijeo Designer, Quantum PLC


Resolution:
The REAL data type variables may not show correctly due to word order not set correctly in Vijeo Designer. When the HMI is communicating to an Unity Quantum PLC the double word order must be "High word first". To change the word order, expand the I/O manager in the navigator and double click on the equipment.

image3

Next, ensure that the Double Word word order is set to "High word first"
image4







Schneider Electric UK

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: