{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
How can we help you today?
How to update an X80 IO card in local rack using EcoStruxure Automation Device Maintenance

Product:

EcoStruxure Automation Device Maintenance (EADM)

Version:

3.1.147

Connection Method :

USB cable

1- Launch EADM

2- Manually add your CPU

Adding the CPU

Adding CPU part 2

3 - Login to the device (at least for firmware download)

Logging in the CPU for firmware access

4 - Go to "Extensions"

Extensions

5 - Manually the X80 IO card

Adding the X80 IO card

6 - The EADM tool will fetch information from that card

Fetching information

7 - Pick the firmware file to use from your database

Picking firmware

8 - Select firmware file

Picking firmware part 2

9 - Start the update

Updating

Schneider Electric UK

Explore more
Product:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Product: