{}

Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
How can we help you today?
How to change the Cipher Suites of an NMC3?

Question :

How to change the Cipher Suites of an NMC3

Product Line / Environment :

Network Management Card 3 – AP9640/AP9641/ AP9643 and/or  Devices with an embedded Network Management Card 3

Answer :

Users may need to adjust the list of SSL/TLS ciphers in use for NMC web access on the NMC, to comply with local security policies, changes in browser compatibility, or to reflect ever-changing best practices.

The option to enable disable Cipher Suites In NMC3 is only accessible via Console or Command line via FTP , SSH or Terminal Emulator (i.e. Putty, TeraTerm) through a USB Connection. Please refer to the Command Line Interface Guide for Network Management Card 3 for details on how to connect via console.

The  command to be used is web with the -cs (meaning Cipher Suite) option. The syntax  would  be "web -cs <level>" specifying the level changes  the tier level of cipher suite that will be used. Value range of 0-4.   Omitting  level value displays current setting.

NOTE: The -cs option is only applied when minimum protocol is set to TLS v1.2 using the -mp option.

Here are the list of what Ciphers are allowed depending on the security level:

apc>web -cs 4

TLS1.2 Cipher Suite Filter:   4

Accepted Cipher Suites:

TLS_ECDHE_ECDSA_WITH_AES_128_GCM_SHA256

TLS_ECDHE_RSA_WITH_AES_128_GCM_SHA256

TLS_DHE_RSA_WITH_AES_128_GCM_SHA256

apc>web -cs 3

TLS1.2 Cipher Suite Filter:   3

Accepted Cipher Suites:

TLS_ECDHE_ECDSA_WITH_AES_128_GCM_SHA256

TLS_ECDHE_RSA_WITH_AES_128_GCM_SHA256

TLS_DHE_RSA_WITH_AES_128_GCM_SHA256

TLS_ECDHE_ECDSA_WITH_AES_128_CBC_SHA256

TLS_ECDHE_RSA_WITH_AES_128_CBC_SHA256

TLS_DHE_RSA_WITH_AES_128_CBC_SHA256

TLS_DHE_RSA_WITH_AES_256_CBC_SHA256

apc>web -cs 2

TLS1.2 Cipher Suite Filter:   2

Accepted Cipher Suites:

TLS_ECDHE_ECDSA_WITH_AES_128_GCM_SHA256

TLS_ECDHE_RSA_WITH_AES_128_GCM_SHA256

TLS_DHE_RSA_WITH_AES_128_GCM_SHA256

TLS_ECDHE_ECDSA_WITH_AES_128_CBC_SHA256

TLS_ECDHE_ECDSA_WITH_AES_128_CBC_SHA

TLS_ECDHE_ECDSA_WITH_AES_256_CBC_SHA

TLS_ECDHE_RSA_WITH_AES_128_CBC_SHA256

TLS_ECDHE_RSA_WITH_AES_128_CBC_SHA

TLS_ECDHE_RSA_WITH_AES_256_CBC_SHA

TLS_DHE_RSA_WITH_AES_128_CBC_SHA256

TLS_DHE_RSA_WITH_AES_256_CBC_SHA256

TLS_DHE_RSA_WITH_AES_128_CBC_SHA

TLS_DHE_RSA_WITH_AES_256_CBC_SHA

apc>web -cs 1

TLS1.2 Cipher Suite Filter:   1

Accepted Cipher Suites:

TLS_ECDHE_ECDSA_WITH_AES_128_GCM_SHA256

TLS_ECDHE_RSA_WITH_AES_128_GCM_SHA256

TLS_DHE_RSA_WITH_AES_128_GCM_SHA256

TLS_RSA_WITH_AES_128_GCM_SHA256

TLS_ECDHE_ECDSA_WITH_AES_128_CBC_SHA256

TLS_ECDHE_ECDSA_WITH_AES_128_CBC_SHA

TLS_ECDHE_ECDSA_WITH_AES_256_CBC_SHA

TLS_ECDHE_RSA_WITH_AES_128_CBC_SHA256

TLS_ECDHE_RSA_WITH_AES_128_CBC_SHA

TLS_ECDHE_RSA_WITH_AES_256_CBC_SHA

TLS_DHE_RSA_WITH_AES_128_CBC_SHA256

TLS_DHE_RSA_WITH_AES_256_CBC_SHA256

TLS_DHE_RSA_WITH_AES_128_CBC_SHA

TLS_DHE_RSA_WITH_AES_256_CBC_SHA

TLS_RSA_WITH_AES_128_CBC_SHA256

TLS_RSA_WITH_AES_256_CBC_SHA256

TLS_RSA_WITH_AES_128_CBC_SHA

TLS_RSA_WITH_AES_256_CBC_SHA

apc>web -cs 0

TLS1.2 Cipher Suite Filter:   0

Accepted Cipher Suites:

TLS_ECDHE_ECDSA_WITH_AES_128_GCM_SHA256

TLS_ECDHE_RSA_WITH_AES_128_GCM_SHA256

TLS_DHE_RSA_WITH_AES_128_GCM_SHA256

TLS_RSA_WITH_AES_128_GCM_SHA256

TLS_ECDHE_ECDSA_WITH_AES_128_CBC_SHA256

TLS_ECDHE_ECDSA_WITH_AES_128_CBC_SHA

TLS_ECDHE_ECDSA_WITH_AES_256_CBC_SHA

TLS_ECDHE_ECDSA_WITH_3DES_EDE_CBC_SHA

TLS_ECDHE_RSA_WITH_AES_128_CBC_SHA256

TLS_ECDHE_RSA_WITH_AES_128_CBC_SHA

TLS_ECDHE_RSA_WITH_AES_256_CBC_SHA

TLS_DHE_RSA_WITH_AES_128_CBC_SHA256

TLS_DHE_RSA_WITH_AES_256_CBC_SHA256

TLS_DHE_RSA_WITH_AES_128_CBC_SHA

TLS_DHE_RSA_WITH_AES_256_CBC_SHA

TLS_DHE_RSA_WITH_3DES_EDE_CBC_SHA

TLS_RSA_WITH_AES_128_CBC_SHA256

TLS_RSA_WITH_AES_256_CBC_SHA256

TLS_RSA_WITH_AES_128_CBC_SHA

TLS_RSA_WITH_AES_256_CBC_SHA

SSL_RSA_WITH_3DES_EDE_CBC_SHA

 Screen shot of  the  Command Line using Putty to Show how the web -cs command is used

Figure 1. Screen shot of  the  Command Line using Putty to Show how the web -cs command is used

For NMC2 Cards Please  Follow FA359198 https://www.apc.com/us/en/faqs/FA359198/

Should there be any other questions, feel free to reach out to us at 800-800-4272 or our chat support group at APC by Schneider Electric Customer Technical Support

Schneider Electric UK

How to change the Cipher Suites of an NMC3?

Question : 

How to change the Cipher Suites of an NMC3

 

Product Line / Environment :

Network Management Card 3 – AP9640/AP9641/ AP9643 and/or  Devices with an embedded Network Management Card 3

 

Answer : 

Users may need to adjust the list of SSL/TLS ciphers in use for NMC web access on the NMC, to comply with local security policies, changes in browser compatibility, or to reflect ever-changing best practices.

 

The option to enable disable Cipher Suites In NMC3 is only accessible via Console or Command line via FTP , SSH or Terminal Emulator (i.e. Putty, TeraTerm) through a USB Connection. Please refer to the Command Line Interface Guide for Network Management Card 3 for details on how to connect via console.

 

The  command to be used is web with the -cs (meaning Cipher Suite) option. The syntax  would  be "web -cs <level>" specifying the level changes  the tier level of cipher suite that will be used. Value range of  0-4.   Omitting  level value displays current setting.

 

NOTE: The -cs option is only applied when minimum protocol is set to TLS v1.2 using the -mp option.

 

Here are the list of what Ciphers are allowed depending on the security level:

 

apc>web -cs 4

TLS1.2 Cipher Suite Filter:   4

Accepted Cipher Suites:

    TLS_ECDHE_ECDSA_WITH_AES_128_GCM_SHA256

    TLS_ECDHE_RSA_WITH_AES_128_GCM_SHA256

    TLS_DHE_RSA_WITH_AES_128_GCM_SHA256

 

apc>web -cs 3

TLS1.2 Cipher Suite Filter:   3

Accepted Cipher Suites:

    TLS_ECDHE_ECDSA_WITH_AES_128_GCM_SHA256

    TLS_ECDHE_RSA_WITH_AES_128_GCM_SHA256

    TLS_DHE_RSA_WITH_AES_128_GCM_SHA256

    TLS_ECDHE_ECDSA_WITH_AES_128_CBC_SHA256

    TLS_ECDHE_RSA_WITH_AES_128_CBC_SHA256

    TLS_DHE_RSA_WITH_AES_128_CBC_SHA256

    TLS_DHE_RSA_WITH_AES_256_CBC_SHA256

 

apc>web -cs 2

TLS1.2 Cipher Suite Filter:   2

Accepted Cipher Suites:

    TLS_ECDHE_ECDSA_WITH_AES_128_GCM_SHA256

    TLS_ECDHE_RSA_WITH_AES_128_GCM_SHA256

    TLS_DHE_RSA_WITH_AES_128_GCM_SHA256

    TLS_ECDHE_ECDSA_WITH_AES_128_CBC_SHA256

    TLS_ECDHE_ECDSA_WITH_AES_128_CBC_SHA

    TLS_ECDHE_ECDSA_WITH_AES_256_CBC_SHA

    TLS_ECDHE_RSA_WITH_AES_128_CBC_SHA256

    TLS_ECDHE_RSA_WITH_AES_128_CBC_SHA

    TLS_ECDHE_RSA_WITH_AES_256_CBC_SHA

    TLS_DHE_RSA_WITH_AES_128_CBC_SHA256

    TLS_DHE_RSA_WITH_AES_256_CBC_SHA256

    TLS_DHE_RSA_WITH_AES_128_CBC_SHA

    TLS_DHE_RSA_WITH_AES_256_CBC_SHA

 

apc>web -cs 1

TLS1.2 Cipher Suite Filter:   1

Accepted Cipher Suites:

    TLS_ECDHE_ECDSA_WITH_AES_128_GCM_SHA256

    TLS_ECDHE_RSA_WITH_AES_128_GCM_SHA256

    TLS_DHE_RSA_WITH_AES_128_GCM_SHA256

    TLS_RSA_WITH_AES_128_GCM_SHA256

    TLS_ECDHE_ECDSA_WITH_AES_128_CBC_SHA256

    TLS_ECDHE_ECDSA_WITH_AES_128_CBC_SHA

    TLS_ECDHE_ECDSA_WITH_AES_256_CBC_SHA

    TLS_ECDHE_RSA_WITH_AES_128_CBC_SHA256

    TLS_ECDHE_RSA_WITH_AES_128_CBC_SHA

    TLS_ECDHE_RSA_WITH_AES_256_CBC_SHA

    TLS_DHE_RSA_WITH_AES_128_CBC_SHA256

    TLS_DHE_RSA_WITH_AES_256_CBC_SHA256

    TLS_DHE_RSA_WITH_AES_128_CBC_SHA

    TLS_DHE_RSA_WITH_AES_256_CBC_SHA

    TLS_RSA_WITH_AES_128_CBC_SHA256

    TLS_RSA_WITH_AES_256_CBC_SHA256

    TLS_RSA_WITH_AES_128_CBC_SHA

    TLS_RSA_WITH_AES_256_CBC_SHA

 

apc>web -cs 0

TLS1.2 Cipher Suite Filter:   0

Accepted Cipher Suites:

    TLS_ECDHE_ECDSA_WITH_AES_128_GCM_SHA256

    TLS_ECDHE_RSA_WITH_AES_128_GCM_SHA256

    TLS_DHE_RSA_WITH_AES_128_GCM_SHA256

    TLS_RSA_WITH_AES_128_GCM_SHA256

    TLS_ECDHE_ECDSA_WITH_AES_128_CBC_SHA256

    TLS_ECDHE_ECDSA_WITH_AES_128_CBC_SHA

    TLS_ECDHE_ECDSA_WITH_AES_256_CBC_SHA

    TLS_ECDHE_ECDSA_WITH_3DES_EDE_CBC_SHA

    TLS_ECDHE_RSA_WITH_AES_128_CBC_SHA256

    TLS_ECDHE_RSA_WITH_AES_128_CBC_SHA

    TLS_ECDHE_RSA_WITH_AES_256_CBC_SHA

    TLS_DHE_RSA_WITH_AES_128_CBC_SHA256

    TLS_DHE_RSA_WITH_AES_256_CBC_SHA256

    TLS_DHE_RSA_WITH_AES_128_CBC_SHA

    TLS_DHE_RSA_WITH_AES_256_CBC_SHA

    TLS_DHE_RSA_WITH_3DES_EDE_CBC_SHA

    TLS_RSA_WITH_AES_128_CBC_SHA256

    TLS_RSA_WITH_AES_256_CBC_SHA256

    TLS_RSA_WITH_AES_128_CBC_SHA

    TLS_RSA_WITH_AES_256_CBC_SHA

    SSL_RSA_WITH_3DES_EDE_CBC_SHA

 

Screen shot of  the  Command Line using Putty to Show how the web -cs command is used

Figure 1. Screen shot of  the  Command Line using Putty to Show how the web -cs command is used

 

For NMC2 Cards Please  Follow FA359198 https://www.apc.com/us/en/faqs/FA359198/

 

Should there be any other questions, feel free to reach out to us at 800-800-4272 or our chat support group at APC by Schneider Electric Customer Technical Support

 

Schneider Electric UK

Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.