Micrologic Trip Unit Type A, P, H and Breaker Communication Module BCM ULP InfraRed LEDs Obsolescence

Due to forced obsolescence on Infra Red LEDs used for communicating between Micrologic Trip Unit and BCM ULP communication module. A new version of Infra LEDs will be used with Micrologic Trip Unit and BCM ULP communication. The new version of Infra LEDs is not backward compatible with existing Micrologic trip units Type A, P, H and BCM ULP. Micrologic Type A, P, H with new Infra Red LEDs will only be compatible with BCM ULP with new Infra Red LEDs. The product commercial references do not change for Micrologic Trip Units and BCM ULP. Product Line Affected: · Masterpact NT / NW · PowerPact P and R

Date: Jul 08 2022 | Type: Product Change Notification
Languages: English | Version: 1.0
Document Number: POW220026