{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
What is the part number for a 4000A plug-in tap box for CP2340G bus duct?
Issue:
Part number for a 4000A plug-in tap box for CP2340G bus duct.

Product Line:
Busway

Environment:
Products sold and used in the United States

Resolution:
Plug-in cable tap boxes are available at a rating of 1600A maximum. These can be installed on 4000A plug-in busway. The catalog number for these is either PTB316GH or PTB316GV depending on the mounting orientation of the busway - if the busway is mounted horizontally use the PTB316GH and if the busway is vertical, use the PTB316GV. End cable tap boxes (CF2340GETBMB) are available for use with CP2340G busway.





Schneider Electric USA

Explore more
Category:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Category: