Issue:
How to choose the correct rated over current protection for a 9070 Type T or TF Control Transformer?
Product Line:
LV Transformer
Resolution:
Over current protection (OCP) is dictated by NEC table 450-3(b). In the European community where they choose to not use the NEC but rather use CE, then it is currently dictated by IEC standard EN 60-742. It is the responsibility of the installer to select the appropriate OCP for the device. Square D does have recommended fuse sizes for the primary and secondary to meet the NEC and/or CE. This is found on pages 10 and 11 of the Industrial Control Transformers (Type T and TF) Catalog, document number 9070CT9901 which is available through Literature Fulfillment and on-line at SquareD.com.
Example: With the 9070TF100D1 being a 100VA, 240 x 480 primary to 120V secondary, using both primary and secondary OCPs, and using page 10 of the aforementioned catalog, the proper primary OCP for 240V applied is 1 amp and for 480V applied is 1/2 amp, and the proper secondary OCP is 1-1/4 amp.
Also from that page, it is shown that the primary fuses are midget type (1-1/2`` x 13/32``) class CC time delay type, and the secondary fuse is a midget type and does not need to be a class CC.
How to choose the correct rated over current protection for a 9070 Type T or TF Control Transformer?
Product Line:
LV Transformer
Resolution:
Over current protection (OCP) is dictated by NEC table 450-3(b). In the European community where they choose to not use the NEC but rather use CE, then it is currently dictated by IEC standard EN 60-742. It is the responsibility of the installer to select the appropriate OCP for the device. Square D does have recommended fuse sizes for the primary and secondary to meet the NEC and/or CE. This is found on pages 10 and 11 of the Industrial Control Transformers (Type T and TF) Catalog, document number 9070CT9901 which is available through Literature Fulfillment and on-line at SquareD.com.
Example: With the 9070TF100D1 being a 100VA, 240 x 480 primary to 120V secondary, using both primary and secondary OCPs, and using page 10 of the aforementioned catalog, the proper primary OCP for 240V applied is 1 amp and for 480V applied is 1/2 amp, and the proper secondary OCP is 1-1/4 amp.
Also from that page, it is shown that the primary fuses are midget type (1-1/2`` x 13/32``) class CC time delay type, and the secondary fuse is a midget type and does not need to be a class CC.
Released for:Schneider Electric USA
Issue:
How to choose the correct rated over current protection for a 9070 Type T or TF Control Transformer?
Product Line:
LV Transformer
Resolution:
Over current protection (OCP) is dictated by NEC table 450-3(b). In the European community where they choose to not use the NEC but rather use CE, then it is currently dictated by IEC standard EN 60-742. It is the responsibility of the installer to select the appropriate OCP for the device. Square D does have recommended fuse sizes for the primary and secondary to meet the NEC and/or CE. This is found on pages 10 and 11 of the Industrial Control Transformers (Type T and TF) Catalog, document number 9070CT9901 which is available through Literature Fulfillment and on-line at SquareD.com.
Example: With the 9070TF100D1 being a 100VA, 240 x 480 primary to 120V secondary, using both primary and secondary OCPs, and using page 10 of the aforementioned catalog, the proper primary OCP for 240V applied is 1 amp and for 480V applied is 1/2 amp, and the proper secondary OCP is 1-1/4 amp.
Also from that page, it is shown that the primary fuses are midget type (1-1/2`` x 13/32``) class CC time delay type, and the secondary fuse is a midget type and does not need to be a class CC.
How to choose the correct rated over current protection for a 9070 Type T or TF Control Transformer?
Product Line:
LV Transformer
Resolution:
Over current protection (OCP) is dictated by NEC table 450-3(b). In the European community where they choose to not use the NEC but rather use CE, then it is currently dictated by IEC standard EN 60-742. It is the responsibility of the installer to select the appropriate OCP for the device. Square D does have recommended fuse sizes for the primary and secondary to meet the NEC and/or CE. This is found on pages 10 and 11 of the Industrial Control Transformers (Type T and TF) Catalog, document number 9070CT9901 which is available through Literature Fulfillment and on-line at SquareD.com.
Example: With the 9070TF100D1 being a 100VA, 240 x 480 primary to 120V secondary, using both primary and secondary OCPs, and using page 10 of the aforementioned catalog, the proper primary OCP for 240V applied is 1 amp and for 480V applied is 1/2 amp, and the proper secondary OCP is 1-1/4 amp.
Also from that page, it is shown that the primary fuses are midget type (1-1/2`` x 13/32``) class CC time delay type, and the secondary fuse is a midget type and does not need to be a class CC.
Released for:Schneider Electric USA



