{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.

How can we help you today?

What is theheat dissipation of the NEMA contactors and starters?

Issue:
What is the thermal out-put for NEMA Sarters?

Product Line:
NEMA and Definite Purpose Contactors and Starters

Environment:
Type S Contactors and Starters

Resolution:
This information is based on internal test data under lab conditions and in no way are our products warranted to this data.

Notes: Values are BTU`s per Hour

8502SA - 34.1 (Series B only)
8502SB - 54.6
8502SC - 68.3
8502SD - 88.7
8502SE - 136.5
8502SF - 225.3
8502SG - 337.9 (Series B only)
8502SH - 1024
8502SJ - Not Available

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: