What is the difference between a 80% rated breaker and a 100% rated breaker?

Issue:
What is the difference between a 80% rated breaker and a 100% rated breaker?
Do we have a list of 100% rated circuit breakers?

Resolution:
For a particular breaker, even though the 80% and 100% versions have the same amp rating (use the same trip curve), in actual use they are applied differently depending on the continuous loads (amount and length of time).

The 80% (standard-rated) breaker can only be applied continuously (defined as 3 hours or more by the NEC) at 80% of its continuous current rating (or Ir setting; e.g. if a 150 A H-frame is dialed to 100 A, the 80% rating applies to the 100 A setting). 100% rated circuit breakers can be applied at up to 100% of their current rating continuously.  Breakers rated at 80% can be applied at 100% of their rating if the loading will last for less than 3 hours.

The following frames have versions that can be 100% rated:

  • Powerpact H frame:  unit mounted only,  with special suffix
  • Powerpact J frame:  unit mounted only,  with special suffix
  • Powerpact L frame:  Unit mounted or ILINE up to 400 amps, with special suffix
  • Powerpact P and R frame, with special suffix
  • Masterpact NT and NW

For further information, see the attached link:
http://blog.schneider-electric.com/datacenter/power-and-cooling/2014/06/12/clearing-confusion-80-vs-100-rated-circuit-breakers/

Schneider Electric USA

What is the difference between a 80% rated breaker and a 100% rated breaker?

Issue:
What is the difference between a 80% rated breaker and a 100% rated breaker?
Do we have a list of 100% rated circuit breakers?

Resolution:
For a particular breaker, even though the 80% and 100% versions have the same amp rating (use the same trip curve), in actual use they are applied differently depending on the continuous loads (amount and length of time).

The 80% (standard-rated) breaker can only be applied continuously (defined as 3 hours or more by the NEC) at 80% of its continuous current rating (or Ir setting; e.g. if a 150 A H-frame is dialed to 100 A, the 80% rating applies to the 100 A setting). 100% rated circuit breakers can be applied at up to 100% of their current rating continuously.  Breakers rated at 80% can be applied at 100% of their rating if the loading will last for less than 3 hours.

The following frames have versions that can be 100% rated:

  • Powerpact H frame:  unit mounted only,  with special suffix
  • Powerpact J frame:  unit mounted only,  with special suffix
  • Powerpact L frame:  Unit mounted or ILINE up to 400 amps, with special suffix
  • Powerpact P and R frame, with special suffix
  • Masterpact NT and NW

For further information, see the attached link:
http://blog.schneider-electric.com/datacenter/power-and-cooling/2014/06/12/clearing-confusion-80-vs-100-rated-circuit-breakers/

Schneider Electric USA

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.