What are the dimensions of 25kV and 38kV HVL Switchgear?
Issue:
Dimensions of 25kV and 38kV HVL Switchgear

Product Line:
Medium voltage switchgear.

Environment:
Products sold in the United States.

Cause:
Product features.

Resolution:
The HVL Switchgear indoor and outdoor enclosures for 25.8kV, 29kV and 38kV have been updated and standardized and have revised dimensions as follows:

Indoor Outdoor
Switch Sections:

Depth 80.50`` (2045mm) 86.00`` (2185mm)

Height 120.00`` (3048mm) 127.00`` (3226mm)

Width 25kV 48.00`` (1220mm) 48.00`` (1220mm)

Width 38kV 60.00`` (1524mm) 60.00`` (1524mm)

Bus Transition Sections:

Width 26.00`` (660mm) 26.00`` (660mm)

Transformer Throats:

Width 24.00`` (610mm) 24.00`` (610mm)

All Meter Sections 25/38kV:

Width 60.00`` (1524mm) 60.00`` (1524mm)




Schneider Electric USA

What are the dimensions of 25kV and 38kV HVL Switchgear?
Issue:
Dimensions of 25kV and 38kV HVL Switchgear

Product Line:
Medium voltage switchgear.

Environment:
Products sold in the United States.

Cause:
Product features.

Resolution:
The HVL Switchgear indoor and outdoor enclosures for 25.8kV, 29kV and 38kV have been updated and standardized and have revised dimensions as follows:

Indoor Outdoor
Switch Sections:

Depth 80.50`` (2045mm) 86.00`` (2185mm)

Height 120.00`` (3048mm) 127.00`` (3226mm)

Width 25kV 48.00`` (1220mm) 48.00`` (1220mm)

Width 38kV 60.00`` (1524mm) 60.00`` (1524mm)

Bus Transition Sections:

Width 26.00`` (660mm) 26.00`` (660mm)

Transformer Throats:

Width 24.00`` (610mm) 24.00`` (610mm)

All Meter Sections 25/38kV:

Width 60.00`` (1524mm) 60.00`` (1524mm)




 

Schneider Electric USA

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.