What fuse type is required for the 8538SB*12/13/22/23/62/65 combination starter?
Issue:
What class of fuses are used with NEMA Size 0 combination starters?
Product Line:
NEMA and Definite Purpose Contactors and Starters
Environment:
8538 type S combination starters
Resolution:
This device is configured from the factory to accept Class H, J, K or R fuse types. However, this device is not supplied with Class R rejection pins. If Class J type (applications above 250 volt) fuses are used it will require re-positioning of the fuse base.
What class of fuses are used with NEMA Size 0 combination starters?
Product Line:
NEMA and Definite Purpose Contactors and Starters
Environment:
8538 type S combination starters
Resolution:
This device is configured from the factory to accept Class H, J, K or R fuse types. However, this device is not supplied with Class R rejection pins. If Class J type (applications above 250 volt) fuses are used it will require re-positioning of the fuse base.
Released for: Schneider Electric USA