Do the breaker enclosures QO2100BNF/S, QO2125BNF/S, QO2100BNRB, QO2125BNRB, QO3100BNF/S, QO3100BNRB need a breaker retaining clip to meet the "Service Entrance" requirement?
Issue:
Application
Product Line:
Enclosed Devices
Environment:
Circuit Breaker Enclosure
Resolution:
No. Service cables connect to the main lugs of the base, not the breaker. This is not back feed application so a retaining method is not required.