Will the PQ3610G plug-in unit install correctly onto a 3P4W busway?
Issue:
PQ3610G plug-in unit installation onto a 3P4W busway

Product Line:
Busway

Environment:
Installation / Setup

Resolution:
Yes. However, there will not be a connection to the neutral bar in the busway. This is true for any plug-in unit up to and including the 600 Amp plug. Above the 600A rating you CANNOT install a 3P plug onto a 4P busway.


Schneider Electric USA

Will the PQ3610G plug-in unit install correctly onto a 3P4W busway?
Issue:
PQ3610G plug-in unit installation onto a 3P4W busway

Product Line:
Busway

Environment:
Installation / Setup

Resolution:
Yes. However, there will not be a connection to the neutral bar in the busway. This is true for any plug-in unit up to and including the 600 Amp plug. Above the 600A rating you CANNOT install a 3P plug onto a 4P busway.


 

Schneider Electric USA

Explore more
Category:
Explore more
Category:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Category:
Explore more
Category:
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.