Issue:
ILINE Panelboard Terminal Data
Product Line:
ILINE Panelboard
Environment:
New and existing ILINE Panelboards
Cause:
Need to select wire for installation or check the terminal data to mean existing wire onsite
Resolution:
Below is the terminal data for all of the panelboards found on page 9-40 in Digest 177, Section 9. Table 9.187 shows the terminal data for the phase and neutral lugs on main lug panels. Table 9.188 shows the standard terminal for main breaker available for ILINE panelboard (please see page 7-41 of Digest 177, Section 7 or page 3-28 of the Supplemental Digest 177, Section 3 for other terminal options for given breakers).
Standard Mechanical Lugs—Main Lugs
ILINE Panelboard Terminal Data
Product Line:
ILINE Panelboard
Environment:
New and existing ILINE Panelboards
Cause:
Need to select wire for installation or check the terminal data to mean existing wire onsite
Resolution:
Below is the terminal data for all of the panelboards found on page 9-40 in Digest 177, Section 9. Table 9.187 shows the terminal data for the phase and neutral lugs on main lug panels. Table 9.188 shows the standard terminal for main breaker available for ILINE panelboard (please see page 7-41 of Digest 177, Section 7 or page 3-28 of the Supplemental Digest 177, Section 3 for other terminal options for given breakers).
Standard Mechanical Lugs—Main Lugs
Amp | Lug Wire Range | Wire Range Wire Bendind Space per NEC Table 373-6 |
225 A | one #6–300 kcmil Al or Cu | one #6–300 kcmil Al or Cu |
400 A | two #2–600 kcmil Al or Cu | one #2–600 kcmil Al or Cu |
600 A | two #2–600 kcmil Al or Cu | two #2–500 kcmil Al or Cu |
800 A | (4) 3/0–750 kcmil Al or Cu | (3) 3/0–500 kcmil Al or Cu |
1200 A | (4) 3/0–750 kcmil Al or Cu | (4) 3/0–500 kcmil Al or Cu |
Standard Mechanical Lugs—Main Circuit Breaker
Amp | Circuit Breaker Type | Lug Wire Range | Wire Range Wire Bendind Space per NEC Table 373-6 |
100 A | FA, FH, FI | one #14-1/0 Al or Cu | one #14-1/0 Al or Cu |
150 A | HD, HG, HJ, HL | one #14-3/0 Al or Cu | one #14-3/0 Al or Cu |
225 A | KI | one #4-300 kcmil Al or Cu | one #4-300 kcmil Al or Cu |
250 A | JD, JG, JJ, JL | one #1/0-#4/0 Al or Cu | one #1/0-300 kcmil Al or Cu |
LX, LXI, LE | two #1-350 kcmil Al or Cu | two #1-350 kcmil Al or Cu | |
400 A | LA, LH | one #1-600 or two #1-250 kcmil Al or Cu | one #1-600 kcmil Al or Cu |
600 A | LC, LI, LX, LXI, LE | two 4/0-500kcmil Al or Cu | two 4/0-500kcmil Al or Cu |
800 A | MG, MJ, PG, PJ, PL | three 3/0-500 kcmil Al or Cu | three 3/0-500 kcmil Al or Cu |
1200 A | PG, PJ, PL, RGC, RJC, RLC | four 3/0-500 kcmil Al or Cu | four 3/0-500 kcmil Al or Cu |