{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
What are the replacement lugs for the LA, LH, and Q4 type circuit breakers?
Product Line:
LA LH Q4 circuit breakers

Resolution:
The standard replacement lugs are catalog number AL400LA, which contains 1 lug per kit.
Several alternate lug kits are available, listed below:

Mechanical Lug Kit
Lug Kit Conductor
AL400LA AL400LAT(1) 1 AWG-600 kcmil AI/Cu (42-304 mm2)
(2) 1 AWG-250 kcmil AI/Cu (42-127 mm2)
CU400LA(1) 1 AWG-600 kcmil Cu (42-304 mm2)
(2) 1 AWG-250 kcmil Cu (42-127 mm2)
AL400LH7
AL400LH7T
(1) 1 350-750 kcmil AI/Cu (177-380 mm2)
AL250LAMC(1) 250-350 kcmil Al (42-304 mm2)
(1) 3/0 AWG-350 kcmil Cu (85-177 mm2)

"T" indicates control wire taps on the lugs.
See instruction bulletin, 48040-896-03

Compression Lugs
Lug KitConductor
VC400LA3(2) #4 AWG-300 kcmil AI/Cu (25-150 mm2)
VC400LA35(2) 250-350 kcmil AI/Cu (120-185 mm2)
VC400LA5(1) #2/0 AWG-500 kcmil AI/Cu (70-240 mm2)
VC400LA7(1) 500-750 kcmil AI (240-400 mm2)
(1) 500 kcmil Cu (240 mm2)
CVC400LA3(2) #2/0 AWG-300 kcmil AI/Cu (70-150 mm2)
CVC400LA5(1) 250-500 kcmil AI/Cu (120-240 mm2)

See instruction bulletin, 48040-699-03

Power Distribution Connectors
Lug KitConductor
PDC4LA250(3) 14-2 AWG Cu, (1) 2 AWG-250 kcmil Cu
PDC6LA20(6)12-2/0 AWG Cu
PDC12LA4(12) 14-4 AWG Cu

See instruction bulletin, 48040-929-04

Schneider Electric USA

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: