Issue:
Convert an existing I line Main Lug Only to a Main Breaker that is vertically mounted
Product Line:
Panelboards
Environment:
I-Line, NEMA 1, Nema 3R
Resolution:
No. There is no way to take the bus assembly apart and change it for this purpose.
A back-fed main-breaker must be used provided the interior is the correct size to accept the required breaker.