Issue:
Maximum breaker for 400amp NF panel.
Product Line:
NF Panelboards
Environment:
Products sold in North America
Resolution:
The maximum branch circuit breaker is 125 amp.
One or two Powerpact J frame, 250 amp maximum, sub-feed breakers can be installed use sub-feed breaker kit NF600SFBJ and the proper back box and trim. The NF600SFBJ requires more mounting space versus the standard enclosure. See the Digest for sizes.