{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
The PBQ3640G is listed for both 240 and 600 volt applications. How does it accommodate both fuse sizes?
Issue:
Fuse base adjustments in the PBQ3640G

Product Line:
I-Line Busway Fusible plug in units

Environment:
Products sold and used in North America

Resolution:
The PBQ3640G is shipped with 600 volt fuse spacing.
The installation instructions provided explain how to relocate the load side fuse bases for use with 240 volt fuses.

Schneider Electric USA

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: