What the DC current contact ratings for the CAD50, CAD32, CAD503, CAD323, CAD506, and CAD326 relay?
Issue:
Checking on the DC current contact ratings for the CAD50, CAD32, CAD503,  CAD323,  CAD506, and  CAD326 relay.

Product Line:
CAD Industrial Relays

Environment:
Relays and Timers

Resolution:
Inductive:
125V DC - 0.55 Amps make and break, 2.5 Amps cont.
250V DC - 0.27 Amps make and break, 2.5 amps cont.
600V DC - 0.10 Amps make and break, 2.5 Amps cont.