What are the torque specifications for the lugs on a PBTB506G plug in tap box?
Issue:
Torque specifications for the lugs on a PBTB506G plug in tap box.
Product Line:
I-Line Busway and Accessories
Environment:
Installation
Cause:
Maintenance
Resolution:
The wire binding screws on the lugs should be torqued to 375 lb-ins, or about 31 lb-ft. See the instruction label on the inside of the device.