{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
How do the Micrologic trip units respond to harmonic loads?
Product Line:
Circuit Breaker Micrologic Trip Units

Resolution:
The Micrologic Trip Unit samples the current waveform to provide true RMS sensing and protection through the 15th harmonic.

Harmonic trip units measure FFT (fast fourier transform) of odd harmonics up to 31st harmonic (percentage of RMS value with respect to RMS value of the fundamental).

Beyond this, the trip units cannot accurately monitor current, so protection is not guaranteed and nuisance tripping is likely.

Schneider Electric USA

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: