Issue:
AP510 busway 10ft replacement section.

Product Line:
I-Line Busway

Environment:
Products sold in North America

Resolution:
You can replace the old busway section with an 8 foot section of new plug-in busway and two, one foot adapters. Catalog numbers are: AF2510G12S for the slot adapter and AF2510G12B is the bolt side adapter. AP2510G8ST is the 8ft plug-in straight piece that goes between them.

It is recommended to use the AT2 assembly tool and HF53F hangers.

Schneider Electric USA

Trying to replace a 10 foot section of AP510 busway. The busway is obsolete, so what can I use?
Issue:
AP510 busway 10ft replacement section.

Product Line:
I-Line Busway

Environment:
Products sold in North America

Resolution:
You can replace the old busway section with an 8 foot section of new plug-in busway and two, one foot adapters. Catalog numbers are: AF2510G12S for the slot adapter and AF2510G12B is the bolt side adapter. AP2510G8ST is the 8ft plug-in straight piece that goes between them.

It is recommended to use the AT2 assembly tool and HF53F hangers.  
 

Schneider Electric USA

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.