{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.

How can we help you today?

Does the trip unit need to be removed to replace the battery on a Masterpact NW?

Article available in these languages: Thai

Issue:
Replacing trip unit battery.
Product Line:
Circuit Breakers Micrologic Trip Units
Resolution:
The battery can be replaced without removing the trip unit. The battery is on the outside edge of the trip unit. The accessory cover must be removed but then the battery can be replaced without removing the trip unit, opening the breaker, etc. Since the door on the equipment and the accessory cover must be removed, the electrician must have the proper PPE (personal protection equipment). The battery is a 7 - 10 year battery and should be replaced during normal maintenance cycles.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: