Issue:
"Failed" indication during Automatic Trip Curve Test with Full Function Test Kit (FFTK)
Product Line:
FFTK for Micrologic A/P/H trip units
Resolution:
This is normal due to the overlapping short time and long time curves. Wait at least 10 seconds after the long time test before performing the short time test.
"Failed" indication during Automatic Trip Curve Test with Full Function Test Kit (FFTK)
Product Line:
FFTK for Micrologic A/P/H trip units
Resolution:
This is normal due to the overlapping short time and long time curves. Wait at least 10 seconds after the long time test before performing the short time test.
Released for:Schneider Electric USA