Issue:
Is it possible to convert in the field the float switches class 9038 type DG to reverse action?
Product Line:
Pressure, Vacuum and Float switches
Environment:
Pressure Switches - Square Dâ„¢ NEMA,
Resolution:
Yes, you can adjust it to ``reverse action`` in the field (contacts close on liquid rise) by attaching the float rod to the projection farthest from the pivot point.
Is it possible to convert in the field the float switches class 9038 type DG to reverse action?
Product Line:
Pressure, Vacuum and Float switches
Environment:
Pressure Switches - Square Dâ„¢ NEMA,
Resolution:
Yes, you can adjust it to ``reverse action`` in the field (contacts close on liquid rise) by attaching the float rod to the projection farthest from the pivot point.
Released for:Schneider Electric USA